Cavity insulation and continuous insulation are different line items
ASHRAE 90.1-2022 uses a specific notation for wall assemblies: R-13 + R-7.5 c.i. means R-13 cavity insulation plus R-7.5 continuous (unbroken by framing) insulation. The "+ c.i." is not a suggestion. It's a code-minimum assembly requirement that demands a separate layer of rigid insulation on the exterior face of the sheathing, continuous across studs, plates, and typically detailed around window openings with taped joints.
A cavity-only R-20 wall and a cavity-plus-c.i. wall that totals R-20 on paper have dramatically different effective thermal performance because of thermal bridging through the steel framing. Per ASHRAE 90.1-2022 Appendix A Table A9.2, a 16-inch-on-center cold-formed steel stud wall with R-13 batt in the cavity delivers an actual U-factor of about 0.124 (effective R-8.1) — not R-13. The parallel-path method and the isothermal-planes method both converge on a 30–40% R-value degradation from thermal bridging. That is why continuous insulation exists in the code at all.
Reading ASHRAE 90.1-2022 Tables 5.5-1 through 5.5-8 correctly
90.1-2022 organizes prescriptive envelope requirements into eight tables, one per climate zone (Zones 1 through 8, with 3C and 5C separated). Each table gives minimum R-value or maximum U-factor for roof, wall, floor, slab, below-grade wall, and opaque door assemblies, broken out by construction class:
- Mass walls (concrete, CMU, precast)
- Metal building walls
- Steel-framed walls
- Wood-framed walls
- Below-grade walls
Reading the wrong construction class is the single most common bid error I see on envelope takeoffs. A steel-framed wall requirement in Climate Zone 5 is R-13 + R-7.5 c.i. A wood-framed wall in the same zone is R-13 + R-3.8 c.i. A mass wall is just R-11.4 c.i. Those are three different product orders, three different labor rates, and three different accessory scopes (furring, Z-girts, thermal clip systems).
R-value targets by climate zone (steel-framed walls, 90.1-2022)
| Climate Zone | Wall Prescriptive | Roof (Insulation Entirely Above Deck) | Slab (Unheated) |
|---|---|---|---|
| Zone 1 | R-13 | R-20 c.i. | NR |
| Zone 2 | R-13 + R-3.8 c.i. | R-25 c.i. | NR |
| Zone 3 | R-13 + R-3.8 c.i. | R-25 c.i. | NR |
| Zone 4 | R-13 + R-7.5 c.i. | R-30 c.i. | R-10 for 24" |
| Zone 5 | R-13 + R-7.5 c.i. | R-30 c.i. | R-10 for 24" |
| Zone 6 | R-13 + R-7.5 c.i. | R-30 c.i. | R-15 for 24" |
| Zone 7 | R-13 + R-15.6 c.i. | R-35 c.i. | R-15 for 24" |
| Zone 8 | R-13 + R-18.8 c.i. | R-35 c.i. | R-20 for 24" |
Numbers are prescriptive minimums per ASHRAE 90.1-2022 Tables 5.5-1 through 5.5-8, steel-framed wall class. Owner-driven specs, LEED, and stretch-code jurisdictions (New York City Local Law 97, Boston's BERDO) routinely add 20–30% over these minimums.
Polyiso LTTR: the aging trap
Polyisocyanurate is the dominant rigid insulation in commercial roofing and continuous-insulation applications because of its high initial R-value per inch (R-6.0 to R-6.5 per inch fresh off the assembly line). That number is not the number you get for the life of the building. Polyiso ages — the blowing agent diffuses out of the cell structure — and the R-value stabilizes at something lower.
The industry-standard aged value is LTTR (Long-Term Thermal Resistance) per CAN/ULC S770 or the PIMA QualityMark program. Typical LTTR values run R-5.5 to R-5.7 per inch at 5 years. That is a roughly 15% drop from the fresh-product R-value. ASHRAE 90.1-2022 Section 5.8.1.8 requires the LTTR value (not the initial value) be used for code compliance calculations on polyiso products.
Example: R-30 c.i. roof, LTTR = 5.7/in → 30 ÷ 5.7 = 5.26 in. → 5.5 in. nominal
Practical implication for takeoff: a spec that calls for "R-30 continuous polyiso" needs to be built out with 5.5 inches of nominal product in a tapered insulation system, not the 4.8 inches you'd get using the fresh R-6.25 value. The difference is a half-inch of thickness across the entire roof. On a 60,000 sf flat roof, that's roughly $18,000–$24,000 of additional polyiso board at current pricing ($1.40–$1.60/bf).
Mineral wool vs polyiso: when the swap pencils
Mineral wool board (Roxul ComfortBoard, Owens Corning Thermafiber) runs R-4.2 per inch, doesn't age, doesn't burn (ASTM E84 Class A flame spread < 25), and is vapor-open. It's a harder sell on fresh-product pricing because you need more thickness for the same rated R-value. But on a continuous-insulation face-sealed assembly where fire rating matters (chase walls, high-rise podiums, Type I-A construction per IBC 2021 Chapter 6), mineral wool frequently wins once you factor the cost of gypsum layers, intumescent treatments, and fire-retardant coatings polyiso needs to achieve the same assembly rating.
Pricing polyiso at fresh R-value (R-6.25/in) instead of LTTR (R-5.5–R-5.7/in). Code compliance demands LTTR. The 10–15% thickness difference compounds across 50,000+ sf of roof or wall — routinely $20,000+ underbid. Always use the manufacturer's PIMA-reported LTTR in the takeoff, not the fresh-product spec sheet.
Vapor retarder placement by climate zone
IBC 2021 Section 1404.3 and IRC R702.7 govern vapor retarder classification and placement. The placement rule is climate-driven and is where takeoffs lose money when estimators substitute product types:
| Climate Zone | Required Placement | Typical Class |
|---|---|---|
| Zone 1–3 | Exterior side or none | Class III (>1.0 perm) |
| Zone 4 (except 4C) | Interior side OR vapor-open assembly | Class II (0.1–1.0 perm) |
| Zone 4C (marine) | No Class I on interior | Class III only |
| Zone 5, 6, 7, 8 | Interior side of thermal insulation | Class I or II (< 0.1 perm) |
The trap: a "kraft-faced batt" is Class II (roughly 0.4 perm). Polyethylene sheet is Class I (0.05 perm). Latex paint on drywall is Class III (3–10 perm). The spec in Section 07 27 00 usually calls out the perm rating explicitly; the schedule and the wall detail may not match. In a cold climate (Zone 6+), an interior polyethylene sheet is fine on paper — but layered with exterior continuous insulation it can create a double-vapor-barrier sandwich that traps moisture in the stud cavity. Building science will catch this before the AHJ does, and the redesign gets priced against the contractor.
Thermal bridging per Appendix A
ASHRAE 90.1-2022 Appendix A provides the calculation methods for effective U-factor of framed wall assemblies accounting for thermal bridging. For takeoff purposes, you don't need to run the Appendix A calc yourself, but you need to know what the engineer did when they set the prescriptive spec. The 90.1-2022 default uses the isothermal-planes method for steel-framed walls, which assumes perfect coupling between the inside face of the sheathing and the outside face of the interior finish — a reasonable approximation when continuous insulation is present, and an aggressive overestimate when it isn't.
Spray foam closed-cell (R-6.5 per inch) and mineral wool exterior c.i. (R-4.2 per inch) both dramatically reduce the thermal bridging penalty. When the envelope engineer has specified closed-cell SPF for the cavity and XPS or polyiso for the exterior c.i., the takeoff needs to price the specific product types called out — they are not interchangeable with batts on cost or thickness.
"The envelope line on a commercial bid is where estimators lose the bid without ever knowing why. The engineer wrote R-13 + R-7.5 c.i. The estimator priced R-20 batt. The submittal reviewer caught it. The GC got the difference as a $58,000 change order at month four. That job didn't have profit in it anymore."
Angela Sims, Envelope Consultant — Simpson Gumpertz & Heger, Boston, MA
The fire-rated insulation scope for chase walls and shafts
IBC 2021 Chapter 7 (Fire and Smoke Protection Features) requires 1-hour to 2-hour rated assemblies around shafts, stair enclosures, and corridor walls in most occupancies. The insulation in those assemblies must carry the rating. Mineral wool achieves this natively (non-combustible per ASTM E136, melting point >2,150°F). Fiberglass batts rated for the assembly must be specified with the UL listing number tied to the assembly type (UL U419, U465, etc.). Polyiso cannot be used in a rated wall assembly without an additional layer of Type X gypsum each side at minimum — a scope that is almost always overlooked on bid day.
For takeoff, pull out the Section 078400 (firestopping) and the UL assembly references on the A-sheets before pricing any insulation in a rated assembly. Get the assembly number right, get the insulation product line right, and confirm the gypsum count on each side of the partition. On a mid-rise building, the rated-assembly insulation scope is typically 12–20% of total insulation cost.
Bottom line
Insulation takeoff is not a sf-times-unit-price exercise. It's a climate zone, an assembly class, a product chemistry, a vapor retarder class, and a fire rating — each of which has a different price tag. Read the ASHRAE 90.1 table row that matches the assembly class, use LTTR for polyiso, confirm vapor retarder placement against the climate zone, and cross-check rated assemblies against the UL listing. Every one of those steps has paid for itself on bids I've run.